 INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-2016-004 3825OhioAvenue,St.Charles,Illinois60174 1-800-SENSOR2,FAX:630-377-6495 www.systemsensor.com
EM-1SRI Supervised Control Module
SPECIFICATIONS NormalOperatingVoltage: StandbyCurrent: AlarmCurrent: MaximumNACCircuitLineLoss: Power Supply Monitor Maximum(Speakers): Maximum(NAC): TroubleRange: MaxNACCurrentRating: TemperatureRange: Humidity: Dimensions: Accessories: BEFORE INSTALLING Thisinformationisincludedasaquickreferenceinstallationguide.Refertotheappropriatecontrolpanelinstallationmanualfordetailedsysteminformation.Ifthemodules willbeinstalledinanexistingoperationalsystem,inform the operator and local authority that the system will be temporarilyoutofservice. NOTICE:Thismanualshouldbeleftwiththeowner/user ofthisequipment. GENERAL DESCRIPTION
15to30VDC 630Amax.average(continuousbroadcasts) 2mA(redLEDon) 4VDC 70.7VRMS.50W Regulated24VDC 0to2VDC ForClassBwiringsystem,3A ForClassAwiringsystem,2A 32Fto120F(0Cto49C) 10to93%RHNoncondensing 4.17Hx4.26Wx1.22D;(106mmHx108mmWx31mmD) 39kEndofLineResistorPart#A2263-00(included) Wallcoverplate(included) SMB500SurfaceMountElectricalBox A2143-60Bypasscapacitor EA-CBControlModuleBarrier noshortexists,thedevicewillreapplytheexternalpower. Thisalgorithm canbe enabledwhen usingaDC external supplythatisguaranteedtobeabove9volts. COMPATIBILITY REQUIREMENTS Toensureproperoperation,thismoduleshallbeconnected toalistedcompatiblecontrolpanel. MOUNTING Themodulemountsdirectlyto4squareelectricalboxes. The box must have a minimum depth of 21/8. Modules mustbemountedwiththearrowfacingupwardforproper operationoftheIRconfigurationtool(modelno.EA-CT). Surface mounted electrical boxes (SMB500) are available fromSystemSensor.
ControlModule,ModelEM-1SRI,isusedtoswitchanexternal power supply or audio amplifier to notification appliances. In addition to switching the external power, the device will monitor the wiring (while external power is notswitchedtotheauxiliarydevices)totheauxiliaryde- WIRING viceforopenandshortcircuitsviaanendoflineresistor. NOTE:Allwiringmustconformtoapplicablelocalcodes, This module is capable of Class A or Class B operation. ordinances,andregulations. Themodulealsohason-boardshortcircuitisolatorstopre- 1. Installmodulewiringinaccordancewiththejobdrawventshortsonthesignalinglinecircuitfromdisablingmore ings and appropriate wiring diagrams. Optional EA-CB thanonedeviceontheintelligentloop. may be required to separate power limited and non power limited wiring in the electrical box (see Figure Thecontrolmodulewillalsohavethecapabilitytomoni1B).2. For new installations usetheenclosed 39 tor the external power input for loss of power (DC voltkEOLresistor.Forretrofitapplicationswheretheexage supplies only). This feature can be disabled through isting47kcannotbeeasilyreplaced,itmaybeleftin device configuration programming. If the external power placewithoutlossofperformance. is switched to the auxiliary devices and there is a loss of the DC supply, the control module has the capability of 3. Settheaddressonthemoduleperjobdrawingsusing theIRconfigurationtool(modelno.EA-CT). runninganalgorithminwhichthedevicewillswitchback to monitor mode and check the line for short circuits. If 4. Securemoduletoelectricalbox(suppliedbyinstaller).
D500-54-00
1
I56-2016-004
Auto Addressing Eclipse Series devices are capable of supporting auto addressing, if the fire alarm control panel is designed to do so.Inautoaddressing,thecontrolpanel,throughtheuse of each device's on-board isolators, can automatically assign device addresses. In order to control which devices areaddressedfirstinwiringconfigurationswithbranches, abranchmarkercanbesetataparticulardevice.Abranch marker is an electronic value from 0 to 255 stored in the device memory. The branch markers are set with the IR configurationtool,EA-CT.
TESTING The following resistance values can be used to test the moduleafterinstallation: ShortCircuit: <50 OpenCircuit: >1M GroundFault: <50
WARNING
Allrelayswitchcontactsareshippedinthestandbystate (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that the switch contactsareintheircorrectstate,modulesmustbemade tocommunicatewiththepanelbeforeconnectingcircuits controlledbythemodule.
Terminal Definitions T1 T2 T3 T4 T7 T8 (+)SLCin/out (-)SLCin/out (+)SLCin/out (-)SLCin/out (-)externalpowerlinein/out (+)externalpowerlinein/out T9 T10 T11 T12 T13 T14 (-)externalpowerlinein/out (+)externalpowerlinein/out NAC(+)A/B NAC(-)A/B NAC(-)ClassA NAC(+)ClassA
Figure 1A: Supervised Control Module
LED INDICATOR IR RECEIVER
Figure 1B: Module mounting with barrier (model no. EA-CB)
C0164-00
C0183-00
D500-54-00
2
I56-2016-004
Figure 2: Typical Class B, Style Y NAC configuration.
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
SIGNAL LINE CIRCUIT (SLC) 30 VDC MAX. TWISTED PAIR RECOMMENDED FROM PANEL OR PREVIOUS DEVICE
MODULE POLARITIES ARE SHOWN IN ALARM
14 13 12 11 10 9 8 7
1 2 3 4
(+) (-) (+) (-)
(-)
EOL RESISTOR
(-)
(+)
24 VDC POWER SUPPLY
+ - + -
(-) (+) (-)
TO NEXT DEVICE
(+)
UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL A77-716B OR EQUIVALENT
(+)
FROM TERMINALS 7 AND 8 OF LAST REQUIRED FOR PANELS CONTROL MODULE ON BRANCH WITHOUT POWER SUPPLY MONITORING
TO NEXT CONTROL MODULE TERMINALS 10 (+) AND 9 (-) OR END OF LINE RELAY (IF REQUIRED)
24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70 LISTED FOR FIRE PROTECTION WITH BATTERY BACK-UP
C0106-04
Figure 3: Typical Class A, Style Z NAC configuration.
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED MODULE POLARITIES ARE SHOWN IN ALARM SIGNAL LINE CIRCUIT (SLC) 30 VDC MAX. TWISTED PAIR RECOMMENDED FROM PANEL OR PREVIOUS DEVICE
14 13
EOL RESISTOR IS INTERNAL AT TERMINALS 13 & 14
1 2 3 4
(+) (-) (+) (-)
(-)
(-)
(+)
24 VDC POWER SUPPLY
12 11 10 9 8 7
+ - + -
(-) (+) (-)
TO NEXT DEVICE
(+)
UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL A77-716B OR EQUIVALENT
(+)
FROM TERMINALS 7 AND 8 OF LAST REQUIRED FOR PANELS CONTROL MODULE ON BRANCH WITHOUT POWER SUPPLY MONITORING
TO NEXT CONTROL MODULE TERMINALS 10 (+) AND 9 (-) OR END OF LINE RELAY (IF REQUIRED)
24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70 LISTED FOR FIRE PROTECTION WITH BATTERY BACK-UP
C0107-04
Figure 4: Typical Class B, Style Y Audio NAC configuration.
ALL WIRING SHOWN IS SUPERVISED SPEAKERS MUST BE LISTED FOR FIRE PROTECTION
SIGNAL LINE CIRCUIT (SLC) 30 VDC MAX. TWISTED PAIR RECOMMENDED FROM PANEL OR PREVIOUS DEVICE
14 13 12
1 2 3 4
(+) (-) (+) (-)
EOL RESISTOR
(+)
AUDIO AMPLIFIER 70.7 Vrms Max. AUDIO CIRCUIT MUST BE TWISTED PAIR AS A MINIMUM WHEN A 70.7 V AUDIO AMPLIFIER IS USED, TERMINALS 1-4 ARE POWER LIMITED, WHILE TERMINALS 7-14 ARE NON-POWER LIMITED
11 10 9 8 7
+ - + -
(-) (+) (-)
TO NEXT DEVICE
TO NEXT CONTROL MODULE LAST MODULE MUST RETURN WIRES
AUDIO AMP.
C0108-01
D500-54-00
3
I56-2016-004
Figure 5: Typical Class A, Style Z Audio NAC configuration.
ALL WIRING SHOWN IS SUPERVISED SIGNAL LINE CIRCUIT (SLC) 30 VDC MAX. TWISTED PAIR RECOMMENDED FROM PANEL OR PREVIOUS DEVICE
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION
14 13 12 11 10 9 8 7
1 2 3 4
(+) (-) (+) (-)
+ - + -
(+)
AUDIO AMPLIFIER 70.7 Vrms Max. EOL RESISTOR IS INTERNAL AT TERMINALS 13 AND 14 REQUIRED BYPASS CAPACITORS: 100F 16V NONPOLARIZED <10A LEAKAGE A2143-60 AUDIO CIRCUIT MUST BE TWISTED PAIR AS A MINIMUM WHEN A 70.7 V AUDIO AMPLIFIER IS USED, TERMINALS 1-4 ARE POWER LIMITED, WHILE TERMINALS 7-14 ARE NON-POWER LIMITED
(-) (+) (-)
TO NEXT DEVICE
TO NEXT CONTROL MODULE LAST MODULE MUST RETURN WIRES
C0109-01
Three-Year Limited Warranty
SystemSensorwarrantsitsenclosedproducttobefreefromdefectsinmaterialsandworkmanshipundernormaluseandserviceforaperiodofthreeyears fromdateofmanufacture.SystemSensormakesnootherexpresswarrantyfor thisairductsmokedetector.Noagent,representative,dealer,oremployeeof theCompanyhastheauthoritytoincreaseoraltertheobligationsorlimitations ofthisWarranty.TheCompany'sobligationofthisWarrantyshallbelimited tothereplacementofanypartoftheproductwhichisfoundtobedefective in materials or workmanship under normal use and service during the three yearperiodcommencingwiththedateofmanufacture.AfterphoningSystem Sensor'stollfreenumber800-SENSOR2(736-7672)foraReturnAuthorization number, send defective units postage prepaid to: System Sensor, Returns Department,RA#__________,3825OhioAvenue,St.Charles,IL60174.Please include a note describing the malfunction and suspected cause of failure. TheCompanyshallnotbeobligatedtoreplaceunitswhicharefoundtobe defectivebecauseofdamage,unreasonableuse,modifications,oralterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any otherWarranty,expressedorimpliedwhatsoever,evenifthelossordamage iscausedbytheCompany'snegligenceorfault.Somestatesdonotallowthe exclusionorlimitationofincidentalorconsequentialdamages,sotheabove limitationorexclusionmaynotapplytoyou.ThisWarrantygivesyouspecific legalrights,andyoumayalsohaveotherrightswhichvaryfromstatetostate.
FCC Statement
Thisdevicecomplieswithpart15oftheFCCRules.Operationissubjecttothefollowingtwoconditions:(1)Thisdevicemaynotcauseharmfulinterference,and(2)thisdevice mustacceptanyinterferencereceived,includinginterferencethatmaycauseundesiredoperation. NOTE:ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdigitaldevice,pursuanttoPart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterferenceinaresidentialinstallation.Thisequipmentgenerates,usesandcanradiateradiofrequencyenergyand,ifnotinstalled andusedinaccordancewiththeinstructions,maycauseharmfulinterferencetoradiocommunications.However,thereisnoguaranteethatinterferencewillnotoccurina particularinstallation.Ifthisequipmentdoescauseharmfulinterferencetoradioortelevisionreception,whichcanbedeterminedbyturningtheequipmentoffandon,theuser isencouragedtotrytocorrecttheinterferencebyoneormoreofthefollowingmeasures: -Reorientorrelocatethereceivingantenna. -Increasetheseparationbetweentheequipmentandreceiver. -Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthereceiverisconnected. -Consultthedealeroranexperiencedradio/TVtechnicianforhelp.
D500-54-00
4
I56-2016-004 (c)2006SystemSensor


▲Up To Search▲   

 
Price & Availability of EM-1SRI

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X